Wiremold Legrand Flamestopper™
Home


Firestopping Through-Wall Cable Penetrations

Flamestopper thru-wall fittings consist of two box assemblies, each with adjustable steel doors. The boxes are attached to EMT conduit, and cables pass through a block of intumescent material inside each assembly. If the temperature reaches approximately 375°F, the material expands, creating a hard char that fills voids around the cables and stops flame from penetrating the opening. When tested to UL 1479 standards, FlameStopper achieved F (flame) and T (temperature) ratings of up to 4 hours. It also earned a low rating for air leakage, making it a highly effective smoke stop.